MIL-PRF-27/344C
Electrical characteristics:
Rated load: With rated voltage across the primary at 400 Hz, the voltage across each winding of
the secondary, wye connected, shall be as specified in Table I within ±5 percent at the current
specified in TableI..
Regulation: Voltage (no load ) Voltage (rated load )
x 100
Voltage (rated load )
TABLE I. Electrical ratings - secondary.
Wye (L-Com) 4 wire 3/
Wye (L-Com) 4 wire 1/
Dash
DC resistance 1/
Delta (L-L) 3 wire 2/
(each winding)
Wye (L-Com)
numbers
(each winding)
(each winding)
M27/344-
Load current
Load current
Volts
Amperes
Volts
Amperes
Ohms ±25%
rms
rms
rms
rms
5
6.00
8.66
3.47
01, 08, 15
.0147
02, 09, 16
.086
12
2.50
20.8
1.45
.135
15
2.00
26.0
1.16
03, 10, 17
20
1.50
34.6
0.87
04, 11, 18
.238
.510
28
1.08
48.5
0.62
05, 12, 19
48
0.63
83.1
0.36
06, 13, 20
1.39
07, 14, 21
8.37
115
0.26
200
0.15
1/ Wye, line to common, connect (6-8-10), load (5-6), (7-6), and (9-6).
2/ Delta, line to line, connect (6-7), (8-9), and (5-10), load (5-7-9).
3/ Wye, line to line, connect (6-10), (8-10), load (5-7-9).
Efficiency (at rated load): Shall be a minimum of 90 percent when computed as follows with
Secondary connected wye, L-Com
(Secondary voltage) (Secondary current)
X 100
(Primary phase voltage)(Primary phase current)
DC resistance (dash numbers 01 through 07):
Primary:
(1-4): 6.8 ohms ±25 percent.
(2-4): 6.8 ohms ±25 percent.
(3-4): 6.8 ohms ±25 percent.
DC resistance (dash numbers 08 through 14):
Primary:
(1-2): 4.53 ohms ±25 percent.
(2-3): 4.53 ohms ±25 percent.
(3-1): 4.53 ohms ±25 percent.
4
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business